BOILERS AND STORAGE BOILERS
RAPID BOILER
- USE: Exchanger for instantaneous production of domestic hot water.
- CONSTRUCTION:outside container for primary fluid in S235JR EN10025 quality steel and inside copper coil for domestic hot water production inside the pipe. Internal diaphragm for the creation of crossed flows of the two fluids.
- INSULATION AND EXTERNAL FINISH: insulation with closed cell polyurethane mat.
- WARRANTY: 5 years against corrosion.
AVAILABLE COLOURS
Grey
HEATING
0
Pmax (bar)
0
Tmax (°C)
0
Pmax (bar) Heat exchanger
MODEL BOLL | 20R | 25R | 30R | 35R | 55R | 85R | |
8 | Effective storage capacity – liters | 2,4 | 4,0 | 8,0 | 14,0 | 15,3 | 16,0 |
d | Tank Diameter – mm | 140 | 152 | 193 | 220 | 220 | 220 |
L | Total Length – mm | 270 | 340 | 400520 | 570 | 620 | |
(*) | Power – Kcal/h | 20000 | 24000 | 30000 | 36000 | 54000 | 81000 |
(*) | Power – Kw | 23,3 | 27,8 | 34,8 | 41,7 | 62,2 | 93,9 |
(*) | Power per hour at 45° – l/h | 700 | 800 | 1000 | 1200 | 1800 | 2400 |
CONNECTIONS | |||||||
EP | Primary circuit inlet | G1” | G1 ¼” | G1 ½” | G2” | G2” | G2” |
UP | Primary circuit outlet | G1” | G1 ¼” | G1 ½” | G2” | G2” | G2” |
ES | Secondary circuit inlet | G ½” | G ½” | G ½” | G ¾” | G ¾” | G ¾” |
US | Secondary circuit outlet | G ½” | G ½” | G ½” | G ¾” | G ¾” | G ¾” |
Sf | Air Hole connection | G ½” | G ½” | G ½” | G ¾” | G ¾” | G ¾” |
Copper pipe diameter – Mm | 12×1 | 12×1 | 14×1 | 16×1 | 16×1 | 18×1 | |
Copper pipe capacity – L | 0,55 | 0,98 | 1,86 | 2,89 | 3,35 | 4,60 | |
TECHNICAL DATA | |||||||
PE | Max pressure – bar | 9 | 9 | 9 | 9 | 9 | 9 |
PC | Testing pressure – bar | 14 | 14 | 14 | 14 | 14 | 14 |
TE | Coil Max Temperature – °C | 100 | 100 | 100 | 100 | 100 | 100 |
PST | Coil Max Pressure – bar | 6 | 6 | 6 | 6 | 6 | 6 |
PCS | Coil Max Testing Pressure – bar | 9 | 9 | 9 | 9 | 9 | 9 |
Weight – Kg | 9 | 12 | 18 | 24 | 26 | 30 |